TeSys LRD thermal overload relays - 16...24 A - class 10A - LRD22
IDR455,200.00
In stock
SKU
LRD22
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
TeSys LRD thermal overload relay, 24A/690V, thermal setting range 16-24A, tripping class 10A, for protection of 3-phase motors 11kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D25-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
| product or component type | differential thermal overload relay |
|---|---|
| range | TeSys |
| device short name | LRD |
| product name | TeSys LRD |
| product compatibility | LC1D25, LC1D32, LC1D38 |
| [Ui] rated insulation voltage | power circuit: 600 V conforming to CSA, power circuit: 600 V conforming to UL, power circuit: 690 V conforming to IEC 60947-4-1 |
| thermal protection adjustment range | 16-24 A |
| network type | AC, DC |
| relay application | motor protection |
| thermal overload class | class 10A conforming to IEC 60947-4-1 |