TeSys D contactor, 3 poles (3NO), for motor control applications up to 40A/690V AC-3 (18.5kW@400V). It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
range of product | TeSys D |
---|---|
product or component type | contactor |
range | TeSys |
device short name | LC1D |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
pole contact composition | 3 NO |
operating time | 12...26 ms closing, 4...19 ms opening |
[Ie] rated operational current | 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
utilisation category | AC-1, AC-3, AC-4 |
[Ue] rated operational voltage | power circuit: <= 300 V DC, power circuit: <= 690 V AC 25...400 Hz |
control circuit type | AC at 50/60 Hz |
poles description | 3P |
contactor application | motor control, resistive load |
product name | TeSys D |
maximum operating rate | 3600 cyc/h 60 °C |
mechanical durability | 6 Mcycles |
product certifications | CCC, CSA, GOST, UL |
power dissipation per pole | 2.4 W AC-3, 5.4 W AC-1 |
average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit |
auxiliary contact composition | 1 NO + 1 NC |
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit, 60 A (at 60 °C) for power circuit |
mounting support | plate, rail |
standards | CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508 |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 800 A at 440 V for power circuit conforming to IEC 60947 |
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1, 80 A gG at <= 690 V coordination type 1 for power circuit, 80 A gG at <= 690 V coordination type 2 for power circuit |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
connections - terminals | control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end, power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end, power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end, power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end, power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end, power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end, power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end |
tightening torque | control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2, power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm, power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm |
electrical durability | 1.4 Mcycles 60 A AC-1 at Ue <= 440 V, 1.5 Mcycles 40 A AC-3 at Ue <= 440 V |
overvoltage category | III |
motor power kW | 11 kW at 220...230 V AC 50/60 Hz (AC-3), 18.5 kW at 380...400 V AC 50/60 Hz (AC-3), 22 kW at 415...440 V AC 50/60 Hz (AC-3), 22 kW at 500 V AC 50/60 Hz (AC-3), 30 kW at 660...690 V AC 50/60 Hz (AC-3), 9 kW at 400 V AC 50/60 Hz (AC-4) |
motor power hp | 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors, 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors, 3 hp at 115 V AC 50/60 Hz for 1 phase motors, 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors, 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors, 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors |
[Ui] rated insulation voltage | power circuit: 600 V CSA certified, power circuit: 600 V UL certified, power circuit: 690 V conforming to IEC 60947-4-1, signalling circuit: 600 V CSA certified, signalling circuit: 600 V UL certified, signalling circuit: 690 V conforming to IEC 60947-1 |
[Icw] rated short-time withstand current | 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 165 A 40 °C - 1 min for power circuit, 320 A 40 °C - 10 s for power circuit, 72 A 40 °C - 10 min for power circuit, 720 A 40 °C - 1 s for power circuit |
protective cover | with |