TeSys GV5 Motor circuit breaker, 3P, 220A, Icu 36kA, thermal magnetic - GV5P220F
IDR7,117,600.00
In stock
SKU
GV5P220F
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
TeSys GV motor circuit breaker, 3 poles (3P), 220A/690V, for protection of 3-phase motors 90-110kW@400V. It provides thermal magnetic protection and additional protections, breaking capacity Icu 36kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors). Thermal protection adjustable by dials with a setting current Ir in range 100-220A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In. Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
range of product | TeSys GV5 |
---|---|
product or component type | motor circuit breaker |
range | TeSys |
device application | motor protection |
device short name | GV5P |
control type | direct rotary handle |
trip unit name | Micrologic 2.2 M |
[In] rated current | 220 A at 65 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
phase failure sensitivity | yes conforming to IEC 60947-4-1 |
product name | TeSys GV5 |
utilisation category | category A conforming to IEC 60947-2 |
breaking capacity | 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 20000 cycles |
magnetic tripping current | 3300-3300 A |
suitability for isolation | yes conforming to EN/IEC 60947-2 |
thermal protection adjustment range | 100-220 A adjustable 9 settings |
poles description | 3P |
protection type | instantaneous short-circuit protection, overload protection, phase loss, phase unbalance, short-circuit protection |
[Isd] short-time pick-up adjustment range | 5...13 x Ir adjustable 9 settings |
trip unit technology | electronic |
power dissipation per pole | 17.6 W |
rated duty | continuous |
breaking capacity code | F 36 kA |
maximum operating rate | 25 cyc/h |
trip unit rating | 220-220 A |
overvoltage category | III |
thermal overload class | class 10 conforming to IEC 60947-4-1, class 20 conforming to IEC 60947-4-1, class 5 conforming to IEC 60947-4-1 |
[Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |