EasyPact EZC400N is a 3 poles fixed circuit breaker designed for the protection of low voltage electrical installations. It is used for standard applications in industries and buildings, offering good performance at competitive price The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 440VAC 50/60Hz or 250VDC. The rating of the thermal-magnetic trip unit is 400A. The trip unit provides fixed overload and instantaneous protections. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. Easypact EZC400N is compliant with international standards (IEC 60947, UL 508) and marine certifications.
range of product | EasyPact |
---|---|
product or component type | circuit breaker |
range | EasyPact |
device application | distribution |
device short name | Easypact EZC400N |
trip unit name | TM-D |
network frequency | 50/60 Hz |
utilisation category | category A |
[Ics] rated service breaking capacity | 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2, 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 20 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 |
[In] rated current | 400 A at 40 °C |
pollution degree | 3 conforming to IEC 60947 |
breaking capacity | 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ue] rated operational voltage | 250 V DC conforming to IEC 60947-2, 440 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | yes conforming to IEC 60947-2 |
trip unit rating | 400-400 A at 50 °C |
network type | AC, DC |
breaking capacity code | N |
poles description | 3P |
protected poles description | 3t |
protection type | overload protection, short-circuit protection |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
product name | EasyPact EZC |
trip unit technology | thermal-magnetic |
circuit breaker name | Easypact EZC400N |