EasyPact EZC circuit breaker EZC100H - TMD - 50 A - 1 pole 1d - EZC100H1050
IDR567,400.00
In stock
SKU
EZC100H1050
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
EasyPact EZC100H is a 1 pole fixed circuit breaker designed for the protection of low voltage electrical installations. It is used for standard applications in industries and buildings, offering good performance at competitive price The breaking capacity (Icu) is 25kA rms at 240VAC 50/60Hz. The operational voltage is 415VAC 50/60Hz or 125VDC. The rating of the thermal-magnetic trip unit is 50A. The trip unit provides fixed overload and instantaneous protections. The dimensions for this 1 pole version are 25mm (W) x 130mm (H) x 60mm (D). Easypact EZC100H is compliant with international standards (IEC 60947, UL 508) and marine certifications.
range of product | EasyPact |
---|---|
product or component type | circuit breaker |
range | EasyPact |
device application | distribution |
device short name | Easypact EZC100H |
trip unit name | TM-D |
network frequency | 50/60 Hz |
utilisation category | category A |
[Ics] rated service breaking capacity | 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA at 125 V DC conforming to IEC 60947-2 |
[In] rated current | 100 A at 40 °C |
pollution degree | 3 conforming to IEC 60664-1, 3 conforming to IEC 947-1 |
breaking capacity | 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2, 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ue] rated operational voltage | 125 V DC conforming to IEC 60947-2, 415 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | yes conforming to IEC 60947-2 |
trip unit rating | 50-50 A at 50 °C |
network type | AC, DC |
breaking capacity code | H |
poles description | 1P |
protected poles description | 1t |
protection type | overload protection, short-circuit protection |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
product name | EasyPact EZC |
trip unit technology | thermal-magnetic |
circuit breaker name | Easypact EZC100H |