TeSys GV4 Motor circuit breaker, 3P, 3.5A, Icu 50kA, thermal magnetic multifunction, Everlink terminals - GV4PEM03N
IDR7,369,800.00
In stock
SKU
GV4PEM03N
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
product or component type | multifunction circuit breaker |
---|---|
range | TeSys |
device application | motor protection |
device short name | GV4PEM |
[In] rated current | 3.5 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
phase failure sensitivity | yes conforming to IEC 60947-4-1 |
product name | TeSys GV4 |
utilisation category | category A |
breaking capacity | 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947, 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947, 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947, 65 kA at 240 V AC 50/60 Hz conforming to UL 60947, Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2, Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, Icu 8 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 800 V conforming to IEC 60947-2 |
mechanical durability | 40000 cycles |
magnetic tripping current | 59-59 A |
suitability for isolation | yes conforming to IEC 60947-1 |
thermal protection adjustment range | 1.4-3.5 A |
poles description | 3P |
protection type | ground fault protection, jam, locked rotor, long start, overload, phase loss, phase unbalance, short time short-circuit protection, short-circuit |
[Isd] short-time pick-up adjustment range | 5...13 x Ir |
trip unit technology | electronic, thermal-magnetic |