Easergy P3 Easergy P3U20, 4L, 1U, 10DI/5DO, Uaux: 48-230V, DI: 110-230V, RS-485 - REL52037
IDR25,578,000.00
In stock
SKU
REL52037
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
range of product | Easergy P3 |
---|---|
product or component type | protection relay |
device short name | P3U20-5AAA2ABAA |
control type | 2 function keys, local control on single-line diagram, local control with I/O keys, local/remote control, mobile application with Easergy SmartApp, programmable logic, programmable switchgear interlocking, switchgear control and monitoring, web-server |
monitoring function | circuit breaker monitoring, relay self-monitoring, trip circuit supervision 74 |
analogue output number | 0 |
analogue input number | 0 |
input type | : 1/5 A CT phase current 3 , : 1/5 A CT residual current 1 , : 100 V/110 V VT voltage 1 |
connections - terminals | clamp terminal removable (current transformer), pin removable (voltage transformer), screw removable (digital input/output) |
network and machine diagnosis type | disturbance recording, event recording, tripping context |
number of outputs | 1 watchdog, 5 |
digital input number | 10 |
setting | 4 |
protection type | breaker failure 50BF, broken conductor 46 I2/I1, capacitor bank unbalance 51C, capacitor overvoltage 59C, cold load pick-up, CT supervision 60, directional earth fault 67N, earth fault overcurrent 50N/51N, excessive starting time, locked rotor 48/51LR, H2 detection 68H2, H5 detection 68H5, lockout relay 86, motor restart inhibition 66, negative sequence overcurrent 46, neutral voltage displacement 59N, phase overcurrent 50/51, phase undercurrent 37, programmable curve, programmable stages 99, recloser 79, switch ON to fault (SOTF), thermal overload protection 49, transient earth fault 67NI, VT supervision 60 |
relay application | universal |
integrated connection type | RS485 1 rear, USB port 1 front |
cybersecurity | password protection, port hardening |
communication port protocol | DeviceNet, DNP3, IEC 60870-5-101, IEC 60870-5-103, Modbus RTU, SPAbus |
number of sensors | 0 arc sensor(s) , 0 temperature sensor(s) |
switchgear diagnosis type | CT supervision, trip circuit supervision ANSI code: TCS |
arc flash protection | no |
single line diagram | 2 controlled + 4 displayed |
type of measurement | active energy, active power, apparent power, condition monitoring CB wear, cos φ, current 2nd, 15th harmonics with THD, current 3-phase, current negative sequence, current phasor diagram view, current positive sequence, current ratio of negative and positive, current zero sequence, earth fault reactance, fault location current, frequency, power angle, power factor, reactive energy, reactive power, RMS active power, RMS apparent power, RMS reactive power, short circuit fault reactance, tan φ, voltage 2nd, 15th harmonics with THD, voltage interruption, voltage negative sequence, voltage phase to earth, voltage phase to phase, voltage phasor diagram view, voltage positive sequence, voltage ratio of negative and positive, voltage zero sequence |
[Us] rated supply voltage | 48...230 V AC/DC |
transmission support medium | copper cable external module, fiber optic cable external module |