range of product Easergy P3
product or component type protection relay
device short name P3U20-5AAA2ACAA
control type 2 function keys, local control on single-line diagram, local control with I/O keys, local/remote control, mobile application with Easergy SmartApp, programmable logic, programmable switchgear interlocking, switchgear control and monitoring, web-server
monitoring function circuit breaker monitoring, relay self-monitoring, trip circuit supervision 74
redundancy communication port protocol PRP, RSTP
analogue output number 0
analogue input number 0
input type : 1/5 A CT phase current 3 , : 1/5 A CT residual current 1 , : 100 V/110 V VT voltage 1
connections - terminals pin removable (current transformer), pin removable (voltage transformer), screw removable (digital input/output)
network and machine diagnosis type disturbance recording, event recording, tripping context
number of outputs 1 watchdog, 5
digital input number 10
setting 4
protection type breaker failure 50BF, broken conductor 46 I2/I1, capacitor bank unbalance 51C, capacitor overvoltage 59C, cold load pick-up, directional earth fault 67N, earth fault overcurrent 50N/51N, earth fault overvoltage 59N, excessive starting time, locked rotor 48/51LR, H2 detection 68H2, H5 detection 68H5, lockout relay 86, motor restart inhibition 66, negative sequence overcurrent 46, phase overcurrent 50/51, phase undercurrent 37, programmable curve, programmable stages 99, rate of change of frequency 81R, recloser 79, switch ON to fault (SOTF), transient earth fault 67NI
relay application universal
integrated connection type RJ45 2 rear, USB port 1 front
cybersecurity password protection, port hardening
communication port protocol DNP3 TCP, Ethernet/IP, IEC 60870-5-101, IEC 61850 ed. 1, IEC 61850 ed. 2, Modbus TCP
number of sensors 0 arc sensor(s) , 0 temperature sensor(s)
switchgear diagnosis type CT supervision ANSI code: 60, trip circuit supervision ANSI code: TCS
arc flash protection no
single line diagram 2 controlled + 4 displayed
type of measurement condition monitoring CB wear, current 2nd, 15th harmonics with THD, current 3-phase, current negative sequence, current phasor diagram view, current positive sequence, current ratio of negative and positive, current zero sequence, earth fault reactance, frequency, voltage zero sequence
[Us] rated supply voltage 48...230 V AC/DC