Easergy P3 Easergy P3U 3CT 1Io 1VT 10DI 5DO 48-230V DI110V 2RJ45 - REL52018
IDR25,596,800.00
In stock
SKU
REL52018
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
range of product | Easergy P3 |
---|---|
product or component type | protection relay |
device short name | P3U20-5AAA2ACAA |
control type | 2 function keys, local control on single-line diagram, local control with I/O keys, local/remote control, mobile application with Easergy SmartApp, programmable logic, programmable switchgear interlocking, switchgear control and monitoring, web-server |
monitoring function | circuit breaker monitoring, relay self-monitoring, trip circuit supervision 74 |
redundancy communication port protocol | PRP, RSTP |
analogue output number | 0 |
analogue input number | 0 |
input type | : 1/5 A CT phase current 3 , : 1/5 A CT residual current 1 , : 100 V/110 V VT voltage 1 |
connections - terminals | pin removable (current transformer), pin removable (voltage transformer), screw removable (digital input/output) |
network and machine diagnosis type | disturbance recording, event recording, tripping context |
number of outputs | 1 watchdog, 5 |
digital input number | 10 |
setting | 4 |
protection type | breaker failure 50BF, broken conductor 46 I2/I1, capacitor bank unbalance 51C, capacitor overvoltage 59C, cold load pick-up, directional earth fault 67N, earth fault overcurrent 50N/51N, earth fault overvoltage 59N, excessive starting time, locked rotor 48/51LR, H2 detection 68H2, H5 detection 68H5, lockout relay 86, motor restart inhibition 66, negative sequence overcurrent 46, phase overcurrent 50/51, phase undercurrent 37, programmable curve, programmable stages 99, rate of change of frequency 81R, recloser 79, switch ON to fault (SOTF), transient earth fault 67NI |
relay application | universal |
integrated connection type | RJ45 2 rear, USB port 1 front |
cybersecurity | password protection, port hardening |
communication port protocol | DNP3 TCP, Ethernet/IP, IEC 60870-5-101, IEC 61850 ed. 1, IEC 61850 ed. 2, Modbus TCP |
number of sensors | 0 arc sensor(s) , 0 temperature sensor(s) |
switchgear diagnosis type | CT supervision ANSI code: 60, trip circuit supervision ANSI code: TCS |
arc flash protection | no |
single line diagram | 2 controlled + 4 displayed |
type of measurement | condition monitoring CB wear, current 2nd, 15th harmonics with THD, current 3-phase, current negative sequence, current phasor diagram view, current positive sequence, current ratio of negative and positive, current zero sequence, earth fault reactance, frequency, voltage zero sequence |
[Us] rated supply voltage | 48...230 V AC/DC |