Easergy P3 Easergy P3U 3CT 1Io 4VT 16DI 8DO 48-230V DI110V 2RJ45 - REL52004
IDR31,856,400.00
In stock
SKU
REL52004
PRE ORDER
Duration Pre-Order : 30
Duration Pre-Order : 30
range of product | Easergy P3 |
---|---|
product or component type | protection relay |
device short name | P3U30-5AAA2BCAA |
control type | 2 function keys, local control on single-line diagram, local control with I/O keys, local/remote control, mobile application with Easergy SmartApp, programmable logic, programmable switchgear interlocking, switchgear control and monitoring, web-server |
monitoring function | circuit breaker monitoring, relay self-monitoring, trip circuit supervision 74 |
redundancy communication port protocol | PRP, RSTP |
analogue output number | 0 |
analogue input number | 0 |
input type | : 1/5 A CT phase current 3 , : 1/5 A CT residual current 1 , : 100 V/110 V VT voltage 4 |
connections - terminals | pin removable (current transformer), pin removable (voltage transformer), screw removable (digital input/output) |
network and machine diagnosis type | disturbance recording, event recording, tripping context |
number of outputs | 1 watchdog, 8 |
digital input number | 16 |
setting | 4 |
protection type | breaker failure 50BF, broken conductor 46 I2/I1, capacitor bank unbalance 51C, capacitor overvoltage 59C, cold load pick-up, CT supervision 60, directional active underpower 37P, directional earth fault 67N, directional phase overcurrent 67, earth fault overcurrent 50N/51N, earth fault overvoltage 59N, excessive starting time, locked rotor 48/51LR, fault locator 21FL, H2 detection 68H2, H5 detection, H5 detection 68H5, lockout relay 86, motor restart inhibition 66, negative sequence overcurrent 46, overvoltage 59, phase overcurrent 50/51, phase undercurrent 37, positive sequence undervoltage 27P, programmable curve, programmable stages 99, rate of change of frequency 81R, recloser 79, switch ON to fault (SOTF), synchro-check 25, transient earth fault 67NI, underfrequency 81/81N, undervoltage 27, VT supervision 60 |
relay application | universal |
integrated connection type | RJ45 2 rear, USB port 1 front |
cybersecurity | password protection, port hardening |
communication port protocol | DNP3 TCP, Ethernet/IP, IEC 60870-5-101, IEC 61850 ed. 1, IEC 61850 ed. 2, Modbus TCP |
number of sensors | 0 arc sensor(s) , 0 temperature sensor(s) |
switchgear diagnosis type | CT supervision, CT/VT supervision ANSI code: 60, trip circuit supervision ANSI code: TCS |
arc flash protection | no |
single line diagram | 4 controlled + 8 displayed |
type of measurement | active energy, active power, apparent power, condition monitoring CB wear, cos φ, current 2nd, 15th harmonics with THD, current 3-phase, current negative sequence, current phasor diagram view, current positive sequence, current ratio of negative and positive, current zero sequence, earth fault reactance, fault location current, frequency, power angle, power factor, reactive energy, reactive power, RMS active power, RMS apparent power, RMS reactive power, short circuit fault reactance, tan φ, voltage 2nd, 15th harmonics with THD, voltage interruption, voltage negative sequence, voltage phase to earth, voltage phase to phase, voltage phasor diagram view, voltage positive sequence, voltage ratio of negative and positive, voltage zero sequence |
[Us] rated supply voltage | 48...230 V AC/DC |